Your Clean Burn Distributor is an expert in recommending the right Clean Burn waste oil furnace for your application. This recommendation includes a wide range of variables and, as you will see as you read further, can be complex. Contact your local Clean Burn Distributor today for a free, full heat loss calculation for your facility.
Air Infiltration: Check for gaps around the doors and windows of the building. A 1” gap around a 12’ x 12’ door is equal to a 1’ x 3’ hole in the sidewall of the building. No heating appliance will be able to adequately heat a “drafty” building.
Building Configuration: A long, narrow building, will be more difficult to heat than a short, more squared building. Example: A 40’ x 50’ building has 180 linear feet of exterior wall surface, while a building 20’ x 100’ has 240 linear feet of exterior wall surface.
Ceiling Height: If the ceiling is more than 14’ high, you must install ceiling fans to re-circulate the heat from the ceiling down onto the floor area. Install one, 3-bladed, 56” industrial ceiling fan every 2,000 square feet of inside building space.
Insulation: A building with no insulation will have a very large heat loss and will be very difficult to heat during the winter months. Also, a building that leaves the garage doors open or one that opens and closes their doors a lot, will require added heat. Make sure that you use the correct correction factor when sizing the equipment in these kinds of situations.
Heat Recovery: A larger heating appliance than is normally required may be necessary to install in a building where the garage doors are left open a lot or opened and closed frequently.
Amount of Waste oil Available: The heating appliance should never be sized by this requirement. It should always by sized by the heat loss of the building. However, if you size the heating appliance based on the amount of waste oil you generate, the heating appliance will not be sized to properly heat the building. It will only be able to supply a portion of the total heat load, and other heat will need to be installed in order to properly heat the building.
IMPORTANT: Do not remove the old heating appliance from the building if it is in proper working order. The old unit can provide auxiliary heat on extremely cold days, and can provide back-up heat should the Clean-Burn unit require service or maintenance.
| Furnace Approx. |
BTU/hr Input |
| CB-140 |
140,000 |
| CB-1750 |
175,000 |
| CB-2500 |
250,000 |
| CB-3250 |
325,000 |
| CB-3500 |
350,000 |
| CB-5000 |
500,000 |
| CB-200-CTB |
200,000 |
| CB-350-CTB | 350,000 |
| CB-500-CTB | 500,000 |
*Note: All furnaces/boilers must be sized by their BTU/hr’s output ratings and not their BTU/hr’s input ratings. If you size them by their listed inputs, you will be undersized and it will not heat the building properly.